Construction Features of the Westinghouse PAM Motor
The same exceptional features that make Westinghouse induction
motors universally
accepted are also among the main reasons the Westinghouse PAM motor has become
the industry choice for two-speed, single-winding induction motors. Some of
the construction features singled out for special consideration are the Thermalastic®
epoxy insulation system, the use of copper/copper alloy rotor construction,
the high-frequency inductionbrazed rotor, the special coating for the laminations,
the construction of the frame, and the top-hat ventilation enclosure.
Thermalastic Epoxy Insulation
The standard insulation system for Westinghouse motors is
the Thermalastic epoxy system, in which an insulation process is used to impregnate
the completely wound and connected stator. Westinghouse developed this innovative
process and has used it in motor production since 1960. No other manufacturer
offers a vacuum pressure post-impregnation system that has been in service
this long.
The Thermalastic insulation system is based on:
o Insulating tape or sheet containing mica-the dielectric material which is
still the best-known insulator.
o Ground wall insulation of mica, applied at conservative voltage stress levels.
Coils are wrapped with mica tape or sheets, and additional layers are applied
in the slots where there will be more stress. Mica is also used on the end
turns.
o Double-braced stator end turns provide extra support. Highly absorbent polyester
pads are placed between the coil diamonds where, after resin impregnation
and curing cycles, these pads harden into rigid arch-lock supports. The coils
are tied to insulated support rings that attach to the outside diameter of
the end turns to ensure a strong mechanical construction.
o Two vacuum pressure impregnation cycles make twice as sure that the entire
stator winding is thoroughly saturated and impregnated with epoxy. For this
manufacturing procedure, the stator is placed into an impregnation tank, where
it is first put under vacuum to remove any air that may be trapped between
the layers of tape. Then, under positive pressure, the entire stator is treated
with epoxy resin to impregnate every possible surface. After the fully impregnated
stator is baked in a curing oven, the epoxy hardens to the toughness of a
reinforced laminate, acting as both a dielectric insulator and bonding agent.
Between end turns, however, a sufficient amount of space remains to allow
cooling air to pass through during motor operation.
Copper
For maximum reliability, Westinghouse has standardized the
use of copper/copper alloy in rotor construction for all large motors.
o Use of copper/copper alloy material for components such as rotor bars and
end rings ensures minimum losses and maximum thermal conductivity.
o Copper and its alloys also offer superior mechanical characteristics, including
a low coefficient of expansion and minimum creep.
o Design flexibility is enhanced by the use of copper. Rotor bars, for example,
can be conservatively sized to allow compact motor dimensions.
Rotor Construction
o High-frequency induction brazing of the rotor bars to
the end rings ensures mechanical integrity and results in uniform strength
and electrical conductivity at the brazed joints. This has been the standard,
proven Westinghouse manufacturing method since 1950 and is still being used
for most rotor sizes.
o Swaged rotor bars minimize bar vibrations and ensure long motor life.
o End rings are centrifugally cast to ensure uniform, void-free, high-integrity
construction.
o For most ratings, the rotor core is attached to the shaft stiffener bar
construction through the use of a shrink fit. This procedure, together with
the welded-on spider construction, assures stable operation under rotational
and thermal forces encountered in service.
Frame
Overall mechanical rigidity minimizes movement, virtually
eliminating the need for realignment and increasing the length of trouble-free,
heavy-duty service.
o Heavy bulkheads and end plates provide solid support for the frame, giving
it both lateral and torsional stability.
o Reinforced end brackets give the bearings rigid support and keep vibration
to a minimum.
o The bearing housing, in line with the end of the frame, provides maximum
bearing stiffness.
Top-Hat Enclosure
The uniform design concept of the top-hat ventilation enclosure combines efficient
cooling with greatly reduced noise levels.
o All airflow for motor cooling takes place well above shaft level, thereby
lessening intake of foreign matter from the surrounding area.
o Foot mounting dimensions are independent of the type of enclosure selected.
The PAM Motor Saves Energy
Many electric utility and industry customers have turned
to the Westinghouse PAM motor to drive fans, pumps, compressors, Banbury mixers
or any other equipment where changing speed provides significant benefits.
Although the applications and the speed combinations are different, the underlying
reason for choosing the PAM motor is always the same: for applications where
a change of speed can offer operating economies, the PAM motor is less costly
to install and more efficient to operate than two-winding motors, two-motor
arrangements or motors with any kind of hydraulic coupling or VFD. For example,
the PAM motor is an efficient power drive for fan applications where either
short or extended periods of operation at less than maximum capacity are required.
Cost Comparison Demonstrates Value
An accurate projection of application economics was made
using the PAM Motor Evaluation Program. The result, based on computer analysis,
is a cost comparison covering a 35-year operating period. In five-year increments,
this projection provides such cost-related data as operating schedules, fixed
costs, energy costs and operating savings-including comparisons between the
dollar investment and the resultant savings for a particular PAM motor. The
results show that a PAM motor, although initially more expensive than a single-speed
motor of comparable rating, typically earns back its investment within one
to three years.
Speed Change Advantages
The PAM motor saves energy costs with its ability to switch
speeds as operating conditions dictate changes in flow rates. In fan and pump
applications, for example, it is this speed change, accomplished without use
of outlet dampers or valves, that is the key to this motor's usefulness. To
illustrate the greater efficiency of the PAM motor over other means of accomodating
variable flow rates, let us look at the three most popular methods: outlet
damper control, inlet vane control and speed control. The simplest way to
change the flow rate is to throttle the system by using inlet vanes or outlet
dampers on fans and suction or discharge valves
on pumps. When such devices are used, the output of the fan or pump is reduced
by the additional pressure drop of the throttling device involved. For example,
a fan with outlet damper control will require 50 percent of rated power input
at 30 percent flow. When using inlet vane control, 30 percent of rated horsepower
will produce 30 percent of rated flow. The most efficient method of varying
the capacity of fans or pumps is to vary their speed, because both the pressure
and the flow are reduced. Using this method, the input power to the fan can
be reduced to approximately 3 percent of rated
horsepower to get 30 percent of output flow. The PAM motor design enables
users to take advantage of this principle. Although a 70 percent variation
in flow may seem extreme, it does illustrate the fundamental point that controlling
flow by varying the speed of the motor is more efficient than throttling at
all flow rates. Speed control is actually more efficient if there is a wide
range in the fluctuation of the flow or if a motor must operate at reduced
load for considerable periods of time. A related advantage of the PAM motor
is that its capability to change speeds allows it to easily accomodate any
future contingencies when the load may have to be changed.
Efficiency Up 20% In Typical Application
A comparison of four methods used to drive a forced draft fan shows that the
PAM motor is most efficient at the maximum continuous rating (MCR) point of
the fan:
First, compare a one-speed, 900 rpm motor where the fan has vane control with
a similar motor that uses a hydraulic coupling. We see that the first combination
is more efficient than the hydraulic coupling control at all points above
75 percent. Although the hydraulic coupling is more efficient below 75 percent,
base load generating stations are not likely to operate in this range. However,
at the probable operating point of 75 percent flow, the PAM motor design (a
two-speed, 900/720 rpm motor where the fan has vane control) results in an
efficiency of about 80 percent compared to only 60 percent for either of the
other two arrangements. A fan operating at this higher efficiency for a number
of years will give you considerable savings in energy costs. Also, the elimination
of the hydraulic coupling with its high initial investment costs, decreased
maintenance costs and use of less floor space will result in additional savings.
Another example shows how a conventional two-speed motor with a 2:1 speed
ratio would perform under similar flow conditions. This kind of comparison
becomes especially meaningful when one considers that fan-type loads are usually
operated at 80 percent of output, and in a single-winding configuration, only
the PAM motor can operate at 720 rpm (the most efficient speed for loads in
that range) and then switch to the 900 rpm speed whenever required. The capability
is available when it is needed.
How the PAM Motor Works
The PAM motor works on a very simple principle: Superimposing
one alternating frequency on another alternating frequency produces both the
sum and the difference of those frequencies. For example: A 900 rpm induction
motor will have an eight-pole fluctuating magnetic wave in the air gap between
the rotor and the stator. So, by doubling up connections on specific coils,
sequenced according to the desired second speed, a second magnetic field will
be produced-in this case, a two-pole field. This
superimposition of a two-pole on an eight-pole field could result in both
the sum and the difference of those two fields, namely a mixture of a ten-pole
and a six-pole field. In the PAM motor, however, we suppress the resultant
six-pole field and keep the original eight-pole field together with the ten-pole
field. The end product of this "Pole Amplitude Modulation" is an
AC induction motor with two predetermined and distinct speeds (900 and 720
rpm in our example). The PAM motor, in fact, differs from conventional AC
induction motors only in its winding design. Actual motor construction details
are identical.
One Winding Does the Job of Two
The PAM motor is not an adjustable speed drive. It is designed to operate
at only two distinct, fixed speeds. While on the one hand, a conventional
single-winding motor can operate at two fixed speeds, the ratio of the speeds
must always be 2:1, which has proven to be practically useless in driving
"fan-type" loads. On the other hand, any two distinct speeds, regardless
of ratio, can always be obtained, but two windings are necessary to accomplish
this, unless the PAM concept is applied.
The advantages related to the PAM motor's single winding versus two winding
machines are:
o Only one winding is needed; it is energized the entire time the motor is
in operation.
o The single-winding design results in an inherently more efficient motor.
o The PAM motor is up to 25 percent lighter and smaller.
The Speed Changing Switch
The most widely accepted speed changing device for the PAM motor is the oil-filled,
five-pole, motor-operated speed changing switch. It is typically installed
close to the motor to minimize cable requirements. There are six leads (three
for each speed) on a PAM motor installation. The PAM motor should be started
on its low-speed winding to limit the inrush current. This prolongs motor
life by keeping rotor and core temperatures to a minimum. Starting on the
low speed is also more desirable for driven equipment considerations. When
starting the motor with the speed changing switch at the low-speed setting,
the main breaker is closed. To change speed once the motor is operating, the
main breaker must be opened, the switch transferred to the other three leads,
and the main breaker closed again. It is important, however, to allow the
magnetic flux in the air gap to decay before finally closing the main breaker.
This pause will take two seconds.