|
|
|
|
Construction Features of the Westinghouse PAM Motor
The same exceptional features that make Westinghouse induction
motors universally
accepted are also among the main reasons the Westinghouse PAM motor has
become
the industry choice for two-speed, single-winding induction motors. Some
of the construction features singled out for special consideration are the
Thermalastic® epoxy insulation system, the use of copper/copper alloy
rotor construction, the high-frequency inductionbrazed rotor, the special
coating for the laminations, the construction of the frame, and the top-hat
ventilation enclosure.
Thermalastic Epoxy Insulation
The standard insulation system for Westinghouse motors
is the Thermalastic epoxy system, in which an insulation process is used
to impregnate the completely wound and connected stator. Westinghouse developed
this innovative process and has used it in motor production since 1960.
No other manufacturer offers a vacuum pressure post-impregnation system
that has been in service this long.
The Thermalastic insulation system is based on:
o Insulating tape or sheet containing mica-the dielectric material which
is still the best-known insulator.
o Ground wall insulation of mica, applied at conservative voltage stress
levels.
Coils are wrapped with mica tape or sheets, and additional layers are applied
in the slots where there will be more stress. Mica is also used on the end
turns.
o Double-braced stator end turns provide extra support. Highly absorbent
polyester pads are placed between the coil diamonds where, after resin impregnation
and curing cycles, these pads harden into rigid arch-lock supports. The
coils are tied to insulated support rings that attach to the outside diameter
of the end turns to ensure a strong mechanical construction.
o Two vacuum pressure impregnation cycles make twice as sure that the entire
stator winding is thoroughly saturated and impregnated with epoxy. For this
manufacturing procedure, the stator is placed into an impregnation tank,
where it is first put under vacuum to remove any air that may be trapped
between the layers of tape. Then, under positive pressure, the entire stator
is treated with epoxy resin to impregnate every possible surface. After
the fully impregnated stator is baked in a curing oven, the epoxy hardens
to the toughness of a reinforced laminate, acting as both a dielectric insulator
and bonding agent. Between end turns, however, a sufficient amount of space
remains to allow cooling air to pass through during motor operation.
Copper
For maximum reliability, Westinghouse has standardized
the use of copper/copper alloy in rotor construction for all large motors.
o Use of copper/copper alloy material for components such as rotor bars
and end rings ensures minimum losses and maximum thermal conductivity.
o Copper and its alloys also offer superior mechanical characteristics,
including a low coefficient of expansion and minimum creep.
o Design flexibility is enhanced by the use of copper. Rotor bars, for example,
can be conservatively sized to allow compact motor dimensions.
Rotor Construction
o High-frequency induction brazing of the rotor bars to
the end rings ensures mechanical integrity and results in uniform strength
and electrical conductivity at the brazed joints. This has been the standard,
proven Westinghouse manufacturing method since 1950 and is still being used
for most rotor sizes.
o Swaged rotor bars minimize bar vibrations and ensure long motor life.
o End rings are centrifugally cast to ensure uniform, void-free, high-integrity
construction.
o For most ratings, the rotor core is attached to the shaft stiffener bar
construction through the use of a shrink fit. This procedure, together with
the welded-on spider construction, assures stable operation under rotational
and thermal forces encountered in service.
Frame
Overall mechanical rigidity minimizes movement, virtually
eliminating the need for realignment and increasing the length of trouble-free,
heavy-duty service.
o Heavy bulkheads and end plates provide solid support for the frame, giving
it both lateral and torsional stability.
o Reinforced end brackets give the bearings rigid support and keep vibration
to a minimum.
o The bearing housing, in line with the end of the frame, provides maximum
bearing stiffness.
Top-Hat Enclosure
The uniform design concept of the top-hat ventilation enclosure combines
efficient cooling with greatly reduced noise levels.
o All airflow for motor cooling takes place well above shaft level, thereby
lessening intake of foreign matter from the surrounding area.
o Foot mounting dimensions are independent of the type of enclosure selected.
The PAM Motor Saves Energy
Many electric utility and industry customers have turned
to the Westinghouse PAM motor to drive fans, pumps, compressors, Banbury
mixers or any other equipment where changing speed provides significant
benefits. Although the applications and the speed combinations are different,
the underlying reason for choosing the PAM motor is always the same: for
applications where a change of speed can offer operating economies, the
PAM motor is less costly to install and more efficient to operate than two-winding
motors, two-motor arrangements or motors with any kind of hydraulic coupling
or VFD. For example, the PAM motor is an efficient power drive for fan applications
where either short or extended periods of operation at less than maximum
capacity are required.
Cost Comparison Demonstrates Value
An accurate projection of application economics was made
using the PAM Motor Evaluation Program. The result, based on computer analysis,
is a cost comparison covering a 35-year operating period. In five-year increments,
this projection provides such cost-related data as operating schedules,
fixed costs, energy costs and operating savings-including comparisons between
the dollar investment and the resultant savings for a particular PAM motor.
The results show that a PAM motor, although initially more expensive than
a single-speed motor of comparable rating, typically earns back its investment
within one to three years.
Speed Change Advantages
The PAM motor saves energy costs with its ability to switch
speeds as operating conditions dictate changes in flow rates. In fan and
pump applications, for example, it is this speed change, accomplished without
use of outlet dampers or valves, that is the key to this motor's usefulness.
To illustrate the greater efficiency of the PAM motor over other means of
accomodating variable flow rates, let us look at the three most popular
methods: outlet damper control, inlet vane control and speed control. The
simplest way to change the flow rate is to throttle the system by using
inlet vanes or outlet dampers on fans and suction
or discharge valves on pumps. When such devices are used, the output of
the fan or pump is reduced by the additional pressure drop of the throttling
device involved. For example, a fan with outlet damper control will require
50 percent of rated power input at 30 percent flow. When using inlet vane
control, 30 percent of rated horsepower will produce 30 percent of rated
flow. The most efficient method of varying the capacity of fans or pumps
is to vary their speed, because both the pressure and the flow are reduced.
Using this method, the input power to the fan can be reduced
to approximately 3 percent of rated horsepower to get
30 percent of output flow. The PAM motor design enables users to take advantage
of this principle. Although a 70 percent variation in flow may seem extreme,
it does illustrate the fundamental point that controlling flow by varying
the speed of the motor is more efficient than throttling at all flow rates.
Speed control is actually more efficient if there is a wide range in the
fluctuation of the flow or if a motor must operate at reduced load for considerable
periods of time. A related advantage of the PAM motor is that its capability
to change speeds allows it to easily accomodate any future contingencies
when the load may have to be changed.
Efficiency Up 20% In Typical Application
A comparison of four methods used to drive a forced draft fan shows that
the PAM motor is most efficient at the maximum continuous rating (MCR) point
of the fan:
First, compare a one-speed, 900 rpm motor where the fan has vane control
with a similar motor that uses a hydraulic coupling. We see that the first
combination is more efficient than the hydraulic coupling control at all
points above 75 percent. Although the hydraulic coupling is more efficient
below 75 percent, base load generating stations are not likely to operate
in this range. However, at the probable operating point of 75 percent flow,
the PAM motor design (a two-speed, 900/720 rpm motor where the fan has vane
control) results in an efficiency of about 80 percent compared to only 60
percent for either of the other two arrangements. A fan operating at this
higher efficiency for a number of years will give you considerable savings
in energy costs. Also, the elimination of the hydraulic coupling with its
high initial investment costs, decreased maintenance costs and use of less
floor space will result in additional savings. Another example shows how
a conventional two-speed motor with a 2:1 speed ratio would perform under
similar flow conditions. This kind of comparison becomes especially meaningful
when one considers that fan-type loads are usually operated at 80 percent
of output, and in a single-winding configuration, only the PAM motor can
operate at 720 rpm (the most efficient speed for loads in that range) and
then switch to the 900 rpm speed whenever required. The capability is available
when it is needed.
How the PAM Motor Works
The PAM motor works on a very simple principle: Superimposing
one alternating frequency on another alternating frequency produces both
the sum and the difference of those frequencies. For example: A 900 rpm
induction motor will have an eight-pole fluctuating magnetic wave in the
air gap between the rotor and the stator. So, by doubling up connections
on specific coils, sequenced according to the desired second speed, a second
magnetic field will be produced-in this case, a two-pole field. This
superimposition of a two-pole on an eight-pole field could result in both
the sum and the difference of those two fields, namely a mixture of a ten-pole
and a six-pole field. In the PAM motor, however, we suppress the resultant
six-pole field and keep the original eight-pole field together with the
ten-pole field. The end product of this "Pole Amplitude Modulation"
is an AC induction motor with two predetermined and distinct speeds (900
and 720 rpm in our example). The PAM motor, in fact, differs from conventional
AC
induction motors only in its winding design. Actual motor construction details
are identical.
One Winding Does the Job of Two
The PAM motor is not an adjustable speed drive. It is designed to operate
at only two distinct, fixed speeds. While on the one hand, a conventional
single-winding motor can operate at two fixed speeds, the ratio of the speeds
must always be 2:1, which has proven to be practically useless in driving
"fan-type" loads. On the other hand, any two distinct speeds,
regardless of ratio, can always be obtained, but two windings are necessary
to accomplish this, unless the PAM concept is applied.
The advantages related to the PAM motor's single winding versus two winding
machines are:
o Only one winding is needed; it is energized the entire time the motor
is in operation.
o The single-winding design results in an inherently more efficient motor.
o The PAM motor is up to 25 percent lighter and smaller.
The Speed Changing Switch
The most widely accepted speed changing device for the PAM motor is the
oil-filled, five-pole, motor-operated speed changing switch. It is typically
installed close to the motor to minimize cable requirements. There are six
leads (three for each speed) on a PAM motor installation. The PAM motor
should be started on its low-speed winding to limit the inrush current.
This prolongs motor life by keeping rotor and core temperatures to a minimum.
Starting on the low speed is also more desirable for driven equipment considerations.
When starting the motor with the speed changing switch at the low-speed
setting, the main breaker is closed. To change speed once the motor is operating,
the main breaker must be opened, the switch transferred to the other three
leads, and the main breaker closed again. It is important, however, to allow
the magnetic flux in the air gap to decay before finally closing the main
breaker. This pause will take two seconds.