Superior 2415G 2000 KW (8 AVAILABLE) can be set up at 50 hz, 13,800 VOLTS, 60 HZ, Superior Model 2416 turbocharged, 4 stroke cycle, Natural gas engine operating @ 1200 rpm, Woodward electronic governor, Switchgear, Engine control panel, gauge panel, Mfgrd: 2000 with 2000 hours each.

Superior Generators

Eight (8) - Cooper Superior Model 2416G-2000 generator sets.
1. Superior Model 2416 turbocharged, 4-stroke cycle, natural gas engine operating at 1000 rpm:

A. Woodward electronic governor
B. Fuel gas injection-each cylinder
C. Engine driven lubricating oil, jacket water, and intercooler pumps
D. High energy capacitor discharge ignition system
E. Intake air filters: heavy-duty dry type
F. Pneumatic Starting motor
G. Exhaust manifold, water-cooled
H. Automatic over speed shutdown
I. Intercooler
J. Engine lube oil sump
K. After-cooler and JW pipes from engine termination plate to radiator termination plate including isolation butterfly valves and flexible couplings.

2. Accessory equipment including..

A. Lubricating oil cooler
B. Lubricating oil filter and strainer
C Lubricating oil thermostat regulating valve
D. Jacket water thermostat regulating valve
F,. Jacket water expansion tank
F. Jacket water radiator
G. Intercooler water Thermostat regulating valve
H. Intercooler water radiator
1. Intercooler water expansion tank
J. Junction boxes, with control wiring termination
K. Peco Fuel Gas Filter
L. Instrument air drier/filter assembly (system)

3. Engine control panel /gauge panel, including:

A. Air-fuel control
B. Engine lube oil pressure gauge
C. Engine Jacket water temperature gauge
D. Engine operating time meter
E. Intercooler water temperature gauge
F. RPM meter
G. Exhaust temperature meter
H. Engine RDU-display unit
I. FT-210 System including computer peripherals.

4. Engine mounted detectors, switches:

A, Overspeed switch
8. Low lube oil pressure switch
C. High jacket water temperature switch
D. High intercooler water temperature switch
E. Low starting air pressure switch
F. Exhaust thermocouples
G. Low oi1 level
H. Low water level

5. A.C. generator, two anti-friction bearings. coupling connected to engine, rated as follows:

KW 2000
KVA 2500
Voltage 11,000
Phase 3
Connected Wye
Hz,, RPM 50,1000
Temp Rise 80"C
Ambient 40"C
Insulation Class F, VPI
Enclosure IP,22
Voltage Regulator Basler

6. A common base for the engine, accessory rack, and generator.

7. Painting - Olive Green 3 stage for corrosive environment

8. Associated items originally shipped loose:

A. Operating and maintenance manuals
Flex connections as follows:
1) Fuel gas supply
2) Jacket water supply
3) Jacket water return
4) Intercooler water supply
5) Intercooler water return
6) Exhaust gas
7) Exhaust flex
8) Critical muffler

B. Anchor bolts

9. Switchgear: Freestanding Six (6) Section Generator Set Metal Clad Medium Voltage Switchgear to provide for power export and utility paralleling, using four (4) 2000KW, 11 KV, 3Phase, 3W, 50 Hz gensets. Switchgear to allow for remote auto start, remote stop, remote diagnostic communication, and auto synch with utility, and will include:

One (1) - Enclosure - NEMA 1 construction for indoor installation with hinged front doors, rear access bolted panels, bottom cable entry. Six (6) vertical sections. Overall dimensions approx. 95"H x 216"W x 94"D.

One (1) - Main Horizontal Bus will be silver-plated copper, rated 1200A, 11Kv, 500MVA and includes 1/4" x 2" ground bus; cable connection to utility, generator and load to be field installed and connected by others.

Five (5) - Vacuum Circuit Breakers, each rated 1200A, 11 KV, SWMVA, 1 SKA rated draw-out type for each generator main,
Breakers include all required line/load compression lugs as required for cable connection; control voltage will be 48VDC from source supplied by others; TOC switch, 2a/2b auxiliary contact included.

One (1) - Neutral Earthing Contactor

.Each Generator Set Controls Section (2) to include.
One (1) - Lot AC Metering, all 1% accuracy and 4 1/2" switchboard size:
1 - Ammeter, 0-300A 1 - Frequency Meter
1 - Voltmeter. 0- 1 SKV 1 - Power Factor Meter
1 - Wattmeter, 0-250OKW 1 - Watt Hour Meter
One (1) - Running Time Meter
Two (2) - Phase Selector Switches, AM & VM
One (1) - Circuit Breaker Control Switch with two (2) CB Status Lamps
One (1) - Surge Suppressant Limiter, 3ph. 11KV
One (1) - Fail to Synch Reset Pushbutton
One (1) - Synch Mode Switch, Auto/Manual
One (1) - DC Control for manual or auto start, including capability to accept customer supplied dry contacts for remote start and remote stop.
Engine Control Switch; 4-position "Auto Manual-Off/Reset-Test"

One (1) - Lot Protective Relays, all sub-panel mounted, industrial grade unless
to include.
· 17/59 - Over/Under Voltage, 1ph
· 3 2 - Reverse Power, 1ph
· SOG - Ground Over current
· 50/51 - Over current, door mounted, utility grade, 3ph. 3W
· 8 1 O/U - Over/Under Frequency
· 47N - Negative Sequence, door mounted, utility grade
· 87G - Generator Differential, door mounted, utility grade

One (l) - Device86-LockoutRelay,48VDC
One (1) - Automatic Voltage Regulator & Overexcitation Breaker
One (1) - Woodward DSLC #9905-228, including VAR/Power Factor Control
One (1) - Woodward #9905-292 Hand-Held DSLC Programmer and Woodward
Speed Controller.
One (1) - Synch Check Relay, Device 25A
One (1) - Frequency Adjusting Raise/Lower Switch
One (1) - Voltage Adjust Motorized Operating Potentiometer
Six (6) - Visual Annunciation of all safety pre-alarm and shutdown conditions
One (1) - Base Load Adjust Switch
One (1) - Pushbutton for Lamp Test/Reset
One (1) - Lot required CT's - Nine (9) ratio as required, plus one (1) ground
fault CT-50:5A.
One (1) - Lot required PTs, fixed mounting for generator controls, 1 00. 1 ration
two (2)
One (1) - Lot Modutec PLC package to include interface with En-Tronic Flex.
Comm. and provide remote diagnostic communication through a modem and phone line Include:

· CPU, 4K with 2MB ports
· 16PT digital input/output modules
· Analogue output module
· Connection cables
· Programming software
· EEProm memory card
· External modem
· Power adapters 22OV, 50Hz
One (1) - Miscellaneous Nameplates, Terminal Blocks, Fuses. fuse Holders,
Control Timers & Relays as required.


Master and Utility Control Section One

One (1) - Lot Utility AC Metering, all 1% accuracy & 4 1/2" switchboard size,
One (1) - Voltmeter
One (1) - Frequency Meter
One (1) - Phase Selector Switch, VM
One (1) - Synchroscope
Two (2) - Synch Lights
One (1) - Synch Source Selector Switch, On/Off

One (1) - Synch Cheek Relay, Device 25
One (1) - System Mode Switch, Auto/Manual
One (1) - Mounting of customer supplied Woodward MSLC, #9905-289, and interconnection of MSILC with individual generator set DSLC systems.
One (1) - Master Fault Alarm Horn with Horn silence Pushbutton
One (1) - Power Supply, 30OW-48VDC to 24VDC for PLC
One (1) - Power Supply, 60OW-48VDC to 24VDC for genset accessories
One (1) - Remote Communication Signal Transducers, to include three (3) Current and
three (3) Voltage, One (1) Kw, One (1)PF, One(1)Frequency and One (1) VAR Transducer for each genset.
One (1) - Discreet Relays and Contacts for remote diagnostic
communication of individual system fault conditions of each Genset
One (1) - VCB Accessories to include manual spring charging lever,
manual racking crank, lifting sling, set draw-out extension rails and one (1) split plug rest jumper.
One (1) - PTs, draw-our mounting for utility controls, ration 60:1
One (1) - Nameplates, Terminal Blocks and other miscellaneous controls as required.

10. One (1) unit mounted sound attenuated enclosure for 60 dBA @ 1 m. Enclosure will be mounted on engine generator base.
Roof mounted mufflers.
Enclosures painted olive green utilizing 3 step process for corrosive environment.

Data for continuous rating only
4-Stroke Cycle, Turbocharged, Intercooled. Equipped for operation on dry natural gas fuel.
2416G
Emissions
Configuration & no. of cylinders Vee 16 NOx 0.90 g/bhp-hr
Bore/Stroke 9.45/10.24 in. CO 2.80 g/bhp-hr
(240/260 mm) NMHC 1.00 g/bhp-hr
Displacement 11,484 cu. in. Heat Rejection Data @ 1200 RPMJack Water Loop
(188 l)
Compression Ratio 10.9:1 Water Flow Rate 494 gpm
BHP 3200 Heat Rejection 68,420 btu/min
Specific Fuel Consumption 6800 btu/bhp-hr JW Temperature Out 180 degrees F
Fuel Quality Range 0-8 NBN value Intercooler and Oil Cooler Loop
Fuel Gas Pressure 45-50 psi Water Flow Rate 494 gpm
Starting Air Pressure 150 psig Heat Rejection 54,400 btu/min
Engine Air Flow Requirement 7860 scfm Supply Temperature Exhaust 130 degrees F
Air Intake Pressure Drop-max. 15 in. H2O Flow Rate 616 lb/min
Exhaust Back Pressure - max. 15 in. H20 Stack Temperature 675 degrees F
BMEP 184 psig Lube Oil Systems - Engine Only 159 gal. ( 600 l)
(12.69 bar) Cooling Water System 185 gal. (700 l)
Speed Rated/Range 1200/900-1200 rpm Engine Weight - Dry (approx.) 39,690 lbs.
Torque 14,005 ft.-lbs. Rotation - from flywheel end Counter-clockwise
Piston Speed @ 1200 rpm 2048 ft./min
Lube Oil Consumption 12,000 bhp-hrs./gal.
Air Manifold Temperature 140 degrees F

SML RESOURCES INTERNATIONAL
FOR INQUIRIES CONTACT
ROY LEADER